Product Details
Proprietary infrared (NDIR) sensor accurately detects the presence of a target gas down to an industry-leading 1 ppm Minimum Detection Level (MDL)
Sensor is not prone to false alarms caused by cross-interference from other gases or sudden changes in temperature or humidity
Gas library contains 60+ refrigerants, including CFCs, HFCs, HCFCs, HFOs and natural refrigerants (R-744, R-717)
Backlit display shows real-time concentration readings and makes configuration and self-diagnostics intuitive
Capable of monitoring up-to 16 zones (expandable up to 48 sample points) and detecting multiple gases with a single monitor
Two optional analog outputs (4-20mA) and Modbus communications (slave) for integration with third-party BMS / BAS control systems
Three user-configurable relays (leak, spill and evacuate) may be used to activate external beacons / sounders, ventilation or other countermeasures
Additional Specifications
- Measuring Range Refrigerants: 0 to 10,000 ppm, Ammonia: 25 to 10,000 ppm Carbon Dioxide: 300 to 8,000 ppm
- Accuracy ±1 ppm ±10% from 0-1000 ppm (refrigerants); ±10 ppm ±10% from 0-10,000 ppm (Ammonia); ±5 PPM ±5% from 300-1000 ppm (CO2)
- Resolution 1 ppm
- Sampling Distance 0 to 1,200' (0 to 365 m)
- Working Temperature Range 32 to 122°F (0 to 50°C)
- Dimensions 13.7" × 12.3" × 5" (350 × 315 × 130 mm)