For use with DMMs, scopemeters and power quality analyzers.
Additional Specifications
- AC Range 1 A to 200 A
- General Accuracy ± 1 % +0.5 A (48 to 65 Hz)
- Bandwidth (-3 dB) 40 Hz to 40 kHz
- Maximum Conductor Diameter 20 mm (0.8")
- Maximum Conductor Size 300 MCM
- Output Levels 10 mV/A, 100 mV/A
- Output Cable 2 m to BNC termination
- Warranty One year
- Safety Rating Cat. III 600 V
- Current Readings AC